ValVue Digital Communications Software Ver. 2.80
90
GE Oil & Gas
Monitor Context Menu
Right-click on the Monitor screen and a context menu appears (Figure 65).
Figure 65 Monitor Screen Context Sensitive Menu
The following items appear and are greyed out based on the actual SVI II AP mode.
Full Open - Moves the valve to full open. This command takes the valve out of closed
loop control and sends a high or low signal to the I/P. This is available only in manual or
setup mode.
Full Closed - Moves the valve to full closed. This takes the valve out of closed loop
control and sends a high or low signal to the I/P. This is available only in manual or
setup mode.
Set to Fail Position - Sets the Output Pressure (P1) to 0 psig. Moves the valve full open or
full closed, whichever is the fail position of the actuator.
Cancel Transfer - Returns the SVI II AP to manual mode from the bumpless transfer
mode (available during a bumpless transfer).
Reset - Issues a master reset to the device, causing it to go through its startup routine
and re-initializing all of its operating parameters from non-volatile memory.
WARNING The valve moves during the reset operation.