Set I/P
Check Screen- Advanced
Set I/P
Setting the I/P removes the valve from normal control and sends a constant, user defined
signal to the I/P. This is useful for troubleshooting. This command is only available in Setup
mode.
To set the I/P:
1. Enter a number between 1 and 55000 in the Set I/P edit box (Figure 136).
2. Right-click and select Set I/P (or use the Tools menu). The indicator appears red.
To resume normal control:
Right-click and select UnSet I/P. Returning to Manual or Normal mode also returns
the valve to control.
Figure 136 Check Screen Context Menu
Set I/P Edit Box
I/P Indicator