GE RAB71B Manual

Busca en linea o descarga Manual para No GE RAB71B. GE RAB71B Architect and Engineering Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 60
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
ARCHITECTS AND ENGINEERS
DESIGN DATA MANUAL
GE Zoneline
®
Packaged Terminal
Air Conditioners
We bring good things to life.
Contract Sales
g
2020 Data Manual 2002 11/7/02 3:19 PM Page 1
Vista de pagina 0
1 2 3 4 5 6 ... 59 60

Indice de contenidos

Pagina 1 - Air Conditioners

ARCHITECTS AND ENGINEERSDESIGN DATA MANUALGE Zoneline®Packaged TerminalAir ConditionersWe bring good things to life.Contract Salesg2020 Data Manual 20

Pagina 2 - Quick Reference

10Indoor Fan Speed Selections - AUTO/HIGHUnit may be operated in HIGH HEAT, AUTO HEAT, HIGH COOL or AUTO COOL.In “AUTO”, the indoor fan will be in low

Pagina 3

11Up-Front Air FiltersTwo up-front filters, easyto remove and reinstall,may be cleaned withoutremoving the room front.Clean by brushing,vacuuming, or

Pagina 4 - DEHUMIDIFICATION*

12Auxiliary Control SwitchesThese switches are located behind the room cabinet under the control panel. 2500 and 3500 SeriesSwitches Description(1) A

Pagina 5 - Important Notice

13Auxiliary Control SwitchesThese switches are located behind the room cabinet under the control panel. 5500 SeriesSwitches Description(1) ALL I2R H

Pagina 6 - Introduction

14Central Desk ControlSome installations may want to govern the ability of the unitto operate from a control device remote to the unit or evenremote t

Pagina 7 - The Zoneline

15Remote Thermostat ControlIn some installations, control of theoperation of the unit at a locationremote to the unit itself may be desired.Unit mount

Pagina 8 - Features Model Series

16Remote Thermostat ControlRAK806 Universal Control Cover LabelWhen a Zoneline unit is using a remote thermostat control, the RAK806 Universal Control

Pagina 9 - Features and Benefits

Remote Thermostat ControlWhen connected to a remote thermostat, the indoor airtemperature sensing is shifted from the unit to the remotethermostat. F

Pagina 10 - Cooling Temperature Limits

18FIELD SUPPLIED RELAY SPECIFICATIONSNUMBER OF RELAY DESIGNATIONUNITS CONTROLLED R1, R2, and R32 POTTER and BRUMFIELD TYPE KA11AY-24 OR EQUIVALENT3 PO

Pagina 11

19Heat Pumps and EnergySavings• GE Zoneline Heat Pumps are designed to provide costefficient heat pump operation while monitoring roomconditions to ma

Pagina 12 - Auxiliary Control Switches

2Quick Reference2500 Series Cooling with Electric HeatMODEL COOLING Cooling Electric Heat Electric Electric Min. CircuitNUMBER (Btuh) Watts EER (Btuh)

Pagina 13

20Heat Pumps and EnergySavings• Heat Pump Operation - Zoneline 5500 SeriesHeat sources: Heat pump, heat pump and simultaneouselectric resistance heat,

Pagina 14 - CDC Terminals

21Application CommentsUse and Care Manual and installation instructions areshipped with Zoneline units. It is important that any airconditioning syste

Pagina 15 - Remote Thermostat Control

22DimensionsRAB71WALL CASEWALL OPENING16-1/4" MIN. x 42-1/4" MIN.RAB77WALL CASEWALL OPENING16-1/2" MIN. x 42-3/8" MIN.WALL CASE WI

Pagina 16

23Wall CaseA choice of wall cases is available for the Zoneline unit.RAB71 - This insulatedcase is constructed ofheavy gauge galvanizedsteel and finis

Pagina 17

24Sub-Base (Cont.)There are separate internal compartments to permitseparation of low voltage (Class 2) connections from linevoltage connections as re

Pagina 18

25Masonry Wall Construction (Cont.)The wall case should be installed during construction andlintels should be used to support the blocks above the wal

Pagina 19 - Heat Pumps and Energy

26FRAMING FOR WALL CASEBRICK VENEER AND FRAME CONSTRUCTIONFASTENING WALL CASEFigure 1 Figure 2MAIN STUDJACK STUDSHEADER – 4" x 4" OR2 - 2&qu

Pagina 20

27WALL SECTION – DETAILED SIDE VIEWFRAME AND BRICK VENEER INSTALLATIONCord Set ConnectedCAULK*Sub-Base ConnectedCAULK*STEEL LINTELRAB71 13-3/4"

Pagina 21 - INCORRECT

28WALL SECTION – DETAILED SIDE VIEWWINDOW, 2" CURTAIN OR PANEL WALL INSTALLATION WITH RAG REAR GRILLE EXTENDED BEYOND OUTER WALL SURFACECord Set

Pagina 22 - Dimensions

29WALL CASE INSTALLATION – CORD SET CONNECTEDEXAMPLE: BLOCK AND VENEER – DIMENSIONAL DATA AND COMMENTSARE ALSO APPLICABLE TO OTHER TYPES OF CONSTRUCTI

Pagina 23 - Sub-Base

3LEGENDCOP – Coefficient of PerformanceEER – Energy Efficient Ratio* – Covers All Model VersionsQuick Reference5500 Series Control Panel5500 Series He

Pagina 24 - Wall Case Installation Data

30METAL CASE EXTENSION FOR WALLS DEEPER THAN 13-1/8" (11-1/8" WITH SUB-BASE)FIELD FABRICATED – GE RECOMMENDS THE USE OF ONE OF THE DEEPER RA

Pagina 25

31ALTERNATE – CASE RECESSION LESS THAN 3" WITH SIDES AND TOPOF WALL OPENING WATERPROOF, FLASHING ON BOTTOM ONLYCAULK*ADIMENSIONS:A. DISTANCE FROM

Pagina 26 - Figure 1 Figure 2

32RAB71/77 WALL CASE INSTALLATION - RAK204 SERIES SUB-BASE CONNECTEDEXAMPLE: FRAME & BRICK VENEER - DIMENSIONAL DATA AND COMMENTSARE ALSO APPLICAB

Pagina 27 - Sub-Base Connected

33RAK204 SERIES SUB-BASE INSTALLATION AND ELECTRICAL DATARAB71/77 WALL CASERAK4002BCHASEWAY OPTION(Shown Without Chassis and Wall Case for Installatio

Pagina 28

34Condensate Disposal Systems Cooling CondensateAir conditioners produce condensate water as a result oflowering the humidity of the area being condit

Pagina 29 - TOP VIEW

35WALL CASE WITH RAD10 DRAIN KITEXTERNAL DRAINSEE PAGE 36 FOR INTERNAL DRAINSEE PAGE 36 NOTE #6SCREWSREARGRILLE“A”METAL“B”PLASTICSQUARE DRAIN HOLESNEO

Pagina 30 - SUPPLIED)

36WALL CASE WITH RAD10 DRAIN KITINTERNAL DRAINSEE PAGE 35 FOR EXTERNAL DRAINSCREWS“A”METAL“B”PLASTICSQUARE DRAIN HOLESNEOPRENE SPONGE GASKETSTEEL MOUN

Pagina 31

37Ducted Installations2500 and 3500 Series Zoneline units may beused in ducted installations.With a ducted installation it is possible to condition th

Pagina 32 - EDGE TO FINISHED

38DUCTED APPLICATION (AZ2500/3500 SERIES)44"DUCT ADAPTER EXTENSION HAS 1/2" INSULATIONNOTES:1. RAK6052 kit includes duct adapter, transition

Pagina 33 - TYPE “A” SCREWS

39DUCTED DETAILED SIDE VIEWS (AZ2500/3500 SERIES)SEE PAGE 38 FOR ALL NOTESLine Cord InstallationCAULK*Sub-Base InstallationANY CONSTRUCTION12-3/4"

Pagina 34 - Condensate Disposal Systems

4The Zoneline 2500, 3500 and 5500 Series have incorporated changes suggested by customers andenhancements by GE’s Technology team: - Auto Heat/Auto C

Pagina 35 - EXTERNAL DRAIN

40Exterior GrillesFour styles of outdoor grilles are available for exteriortreatments. The standard stamped aluminum grille(RAG60), the molded archite

Pagina 36 - INTERNAL DRAIN

41Power Connection For DeluxeSeries (2500 & 3500)The Zoneline 2500 and 3500 Series units have discrete heaterwattages. Each unit has a factory ins

Pagina 37 - Mounting Collar and Register

42Power Connection Kits ForPremium Series (5500) The Zoneline 5500 Series units are connected to thebuilding power supply by a unique power connection

Pagina 38 - 7-3/8"

43Power Connection Kits ForPremium Series (5500)265 or 277 Volt InstallationsNational Electrical Code (Article 440 section G) requirespermanent connec

Pagina 39 - Sub-Base Installation

44Maximum Connected Load For Deluxe Series (2500 and 3500) The maximum connected load of a Zoneline unit occurs when the unit is in resistance heating

Pagina 40 - Outdoor Grilles

45Cooling Performance DataHeat Pump Performance DataTotal Capacity - BTU/Hr. BTUH At 80°F D.B. - 67°F W.B.Temperatureof Air EnteringCondenser7582859

Pagina 41 - Series (2500 & 3500)

46Latent System CapacityThe total capacity of an air conditioner is made up of theSensible capacity, the output of the unit used to remove heatfrom th

Pagina 42 - Premium Series (5500)

47Normal Yearly Operating DataFormula for Calculating Operating Costs Using Above Data:Heating* -

Pagina 43

48MAINBOARDUNITCN1ORORYLYLID. COILROOM123456CN5CN312CN2CN104WHWHYLYLCN103BKBKTRANSFORMERRY103BKRDBKWHRDCN101CN1021351351257DRIVEBOARDUNITRY102 RY101CN

Pagina 44

49MAINBOARDUNITCN1ORORYLYLID. COILROOM123456CN5CN312CN2CN104WHWHYLYLCN103BKBKTRANSFORMERRY103BKRDBKWHRDCN101CN1021351351257DRIVEBOARDUNITRY102 RY101CN

Pagina 45 - Heat Pump Performance Data

5Table of ContentsFront Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 46 - Latent System Capacity

5012345678910YLYLORORBKBKBLBLRDRDROOMID. COILOD. COILOUTDOORHEATERCN1MAIN BOARD UNITCN5CN2CN104CN6 & 712CN3WHWHYLYLBKBK1257CN103OPERATIONBOARD UNI

Pagina 47 - Normal Yearly Operating Data

51Suggested Bid FormSpecifications The following are suggested specifications for the Zoneline 2500Series Packaged Terminal Air Conditioner, the 3500

Pagina 48 - MAIN BOARD UNIT

52Additional specifications for GE Zoneline 3500 Series PackagedTerminal Heat Pump (for 5500 series units use specificationsnoted for 5500 series ins

Pagina 49 - ICR BOARD UNIT

53Wall Cases and Grilles are needed for new installations Alternate specification for steel wall case.Wall case shall be constructed of heavy gauge,

Pagina 50

54Deluxe Line: 2500,Dry Air 25 & 3500 Series - Models are manufactured with fixed heaterwattages with the appropriate power cordattached (all 265

Pagina 51 - Specifications

55Receptacles/Sub-BasesTandem230/208V 15 AmpNEMA6-20RPerpendicular230/208V 20 AmpNEMA6-20RLarge Tandem230/208V 30 AmpNEMA6-30R265V 15 AmpNEMA7-15R;re

Pagina 52

56Kit Number Description For Additional Information Refer to PageRAA62A Spare filters for AZ25, AZ35, and AZ55 Models (10 per box) 10RAB71 Steel Wall

Pagina 53

57General InstallationSuggestionsMany times poor or non-existent caulking around theexterior of the wall case results in air infiltration causing theu

Pagina 54 - Chassis Nomenclature

58Ducted Installation CommentsNew Installations The GE Zoneline 2500 and 3500 series are approved forducted installation using the GE Duct Adapter mod

Pagina 55 - Receptacles/Sub-Bases

59Alphabetical IndexCategory Page No.Accessory List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 56 - Complete Accessory List

6IntroductionThis manual is designed to provide product, performanceand application information to our customers and theirarchitects and engineers for

Pagina 57 - Suggestions

ZONELINEWARRANTYStaple sales slip or cancelled check here. Proof of originalpurchase date is needed to obtain service under warranty.For service in th

Pagina 58 - Ducted Installation Comments

7The Zoneline®SystemThe typical Zoneline installation consists of the wall case (or sleeve), chassis, and exterior grille. Some installations may use

Pagina 59 - Alphabetical Index

8Zoneline®Features Model SeriesAZ AZ AZ2500 3500 5500Enhanced Dehumidification - Dry Air 25 Optional N/A N/ACooling EER Range (230 Volts/265 Volts) 9.

Pagina 60 - GEAppliances.com

9Features and BenefitsStandard Physical DimensionsGE has maintained the same dimension since 1961- 42" widex 16” high x 13 3/4" deep.Replace

Comentarios a estos manuales

Sin comentarios